Home | Sef 100 Alarms Numbers 20.5 to 40 | Sef 100 Proportional Output Board - Board 13 | Series 7 Troubleshooting | SEF100 Electronic Boards Part Numbers | SEF 100 Option Selection | Sef 100 System Fundamentals | Series 8 AT Hydraulic Diagrams - Circuit Diagrams | Sandretto Items For Sale | Mirco Machines | NA | Master Alarm Listing | Sef 100 Master Alarm Listing 30 to 59 | Master Sef 100 Alarm listing alarms 01-29 | Series 8 Sef 100 Tonnage Boost | Series 8 Sef 100 Analog Linear Transducer Board Dip Switch Setup | Series 8 AT Technical Specs | Sef 100 Configuration list | Technical documents | Troubleshooting guides | Machine Technical documents | Other information | Additional Troubleshooting Guides | Mega T, TE and Other Technical
The Sandretto Molding Machine Mechanic Helper

Master Sef 100 Alarm listing alarms 01-29

Enter subhead content here

Master alarm list for Mega T program version 770 to 775
Lev Exc Alarm  Alarm description cause of alarm
1st byte 2nd byte Number
1.1 Nozzle temperature : very low
1.2 Nozzle temperature: low
1.3 Nozzle temperature: high
1.4 Nozzle temperature: very high
1.5 Nozzle temperature : out of range
1.6 Nozzle thermocouple anomally The system checks the temperature rise or setpoint with the heaters on.  If the heaters
do not increase its temperature (when the controller is calling for heating) by 2'C in 3 minutes then this alarm appears
Or a sudden temperature change in any of the barrel zones will generated this alarm.
2.1 Barrel zone A temperature: low
2.2 Barrel zone A temperature: low
2.3 Barrel zone A temperature: high
2.4 Barrel zone A temperature: very high
2.5 Barrel zone A temperature: out of range
2.6 Barrel zone A temperature: anomally The system checks the temperature rise or setpoint with the heaters on.  If the heaters
do not increase its temperature (when the controller is calling for heating) by 2'C in 3 minutes then this alarm appears
Or a sudden temperature change in any of the barrel zones will generated this alarm.
3.1 Barrel zone B temperature: low
3.2 Barrel zone B temperature: low
3.3 Barrel zone B temperature: high
3.4 Barrel zone B temperature: very high
3.5 Barrel zone B temperature: out of range
3.6 Barrel zone B temperature: anomally The system checks the temperature rise or setpoint with the heaters on.  If the heaters
do not increase its temperature (when the controller is calling for heating) by 2'C in 3 minutes then this alarm appears
Or a sudden temperature change in any of the barrel zones will generated this alarm.
4.1 Barrel zone C temperature: low
4.2 Barrel zone C temperature: low
4.3 Barrel zone C temperature: high
4.4 Barrel zone C temperature: very high
4.5 Barrel zone C temperature: out of range
4.6 Barrel zone C temperature: anomally The system checks the temperature rise or setpoint with the heaters on.  If the heaters
do not increase its temperature (when the controller is calling for heating) by 2'C in 3 minutes then this alarm appears
Or a sudden temperature change in any of the barrel zones will generated this alarm.
5.1 Barrel zone D temperature: low
5.2 Barrel zone D temperature: low
5.3 Barrel zone D temperature: high
5.4 Barrel zone D temperature: very high
5.5 Barrel zone D temperature: out of range
5.6 Barrel zone D temperature: anomally The system checks the temperature rise or setpoint with the heaters on.  If the heaters
do not increase its temperature (when the controller is calling for heating) by 2'C in 3 minutes then this alarm appears
Or a sudden temperature change in any of the barrel zones will generated this alarm.
6.1 Barrel zone E temperature: low
6.2 Barrel zone E temperature: low
6.3 Barrel zone E temperature: high
6.4 Barrel zone E temperature: very high
6.5 Barrel zone E temperature: out of range
6.6 Barrel zone E temperature: anomally The system checks the temperature rise or setpoint with the heaters on.  If the heaters
do not increase its temperature (when the controller is calling for heating) by 2'C in 3 minutes then this alarm appears
Or a sudden temperature change in any of the barrel zones will generated this alarm.
7.1 Barrel zone 1 interm. Temp: very low
7.2 Barrel zone 1 interm temp: low
7.3 Barrel zone 1 interm temp: low
7.4 Barrel zone 1 interm temp: high 
7.5 Barrel zone 1 interm temp: out of range
7.6 Barrel zone 1 interm temp: anomally The system checks the temperature rise or setpoint with the heaters on.  If the heaters
do not increase its temperature (when the controller is calling for heating) by 2'C in 3 minutes then this alarm appears
Or a sudden temperature change in any of the barrel zones will generated this alarm.
8.1 Barrel zone 1 temp: very low
8.2 Barrel zone 1 temp: low
8.3 Barrel zone 1 temp: high
8.4 Barrel zone 1 temp: very high
8.5 Barrel zone 1 temp: out of range
8.6 Barrel zone 1 temp: anomally The system checks the temperature rise or setpoint with the heaters on.  If the heaters
do not increase its temperature (when the controller is calling for heating) by 2'C in 3 minutes then this alarm appears
Or a sudden temperature change in any of the barrel zones will generated this alarm.
9.1 Barrel zone 2 temp: very low
9.2 Barrel zone 2 temp: low
9.3 Barrel zone 2 temp: high
9.4 Barrel zone 2 temp: very high
9.5 Barrel zone 2 temp: out of range
9.6 Barrel zone 2 temp: anomally The system checks the temperature rise or setpoint with the heaters on.  If the heaters
do not increase its temperature (when the controller is calling for heating) by 2'C in 3 minutes then this alarm appears
Or a sudden temperature change in any of the barrel zones will generated this alarm.
10.1 Barrel zone 3 temp: very low
10.2 Barrel zone 3 temp: low
10.3 Barrel zone 3 temp: high
10.4 Barrel zone 3 temp: very high
10.5 Barrel zone 3 temp: out of range
10.6 Barrel zone 3 temp: anomally The system checks the temperature rise or setpoint with the heaters on.  If the heaters
do not increase its temperature (when the controller is calling for heating) by 2'C in 3 minutes then this alarm appears
Or a sudden temperature change in any of the barrel zones will generated this alarm.
11.1 Barrel zone 4 temp: very low
11.2 Barrel zone 4 temp: low
11.3 Barrel zone 4 temp: high
11.4 Barrel zone 4 temp: very high
11.5 Barrel zone 4 temp: out of range
11.6 Barrel zone 4 temp: anomally The system checks the temperature rise or setpoint with the heaters on.  If the heaters
do not increase its temperature (when the controller is calling for heating) by 2'C in 3 minutes then this alarm appears
Or a sudden temperature change in any of the barrel zones will generated this alarm.
3 2 + 8  12.1 Lubrication oil network: level insufficient
13.1 Lubrication oil network: pressure insufficient
14.1 Lubrication oil network failure
15.1 Lubrication oil level inadequate
16.1 Hydraulic oil suction filters obstructed
17.1 Hydraulic oil temperature: lowest
17.2 Hydraulic oil temperature: very low
17.3 Hydraulic oil temperature: low
17.4 Hydraulic oil temperature: high
17.5 Hydraulic oil temperature: very high
17.6 Hydraulic oil temperature: highest 
18.1 Mold closing not complete The mold didn't complete it's closing stroke before the internal timer expired
18.2 Mold closing in safety pressure condition not completed The mold didn't complete it's low pressure closing sequence
18.3 Mold closing not complete, no low pressure completed FC 
18.4 Compression not completed The mold compression didn't excuted 
18.5 Tailstock distension not completed
18.6 Mold not ejected
18.7
18.8 Mold fitted
18.9 Mold not fitted
19
19.1 Mold opening not completed The mold didn't make the Q03 Opening end position.
19.2 Premovement not completed The mold didn'[t complete it's Q04 position
19.3 Mold opening for breathe not completed. The mold didn't open to the Q37 position to complete it's breathe operation 
19.4 Tailstock release not completed
19.5 Moving platen opening not completed
19.6 Moving platen opening not correct
19.7 Premovement impossible, ejector consent missing Q04 Premovement end position can't function because the ejector are not fully retracted.
19.8 Premovement impossible, robot enabled Q04 Premovement end position has a value enter lower than maximum mold opening stroke.  You can't use premovement with the robot
19.9 Mold in position
20.1 Injection carriage approach not completed The carriage didn't make the Q17 Carriage forward position. 
20.2 Injection carriage backward not completed The carriage didn't make the Q16 Carriage backward position.
20.3 Safety device activated: carriage piston unhooked The carriage clevis pins are not inserted, check the SQ 18 limit switches
20.4 Nozzle purge not completed
20.5 Safety device activated: injection group rotated The injection unit is out of position For the Mega T it's SQ-26 limit switch
20.6 Safety device activated: mold not closed
20.7 Injection carriage not back The carriage didn't make the Q16 Carriage backward position.
21.1 Injection not completed Injection didn't changeover from first stage to second stage before D04 timer expired.
21.2 Incorrect injection changeover advanced in 2nd stage
21.3 Injection injection:changeover delayed in 2nd stage
21.4 Injection not executed:low accumulator pressure
21.5 Injection not executed:mold not closed The Injection sequence doesn't start because the mold position didn't make the Q09 position
21.6
21.7
21.8
21.9
22.1 Ejection sequence not possible mold consent missing
22.2 Ejection sequence not possible : core pulling consent missed
22.3 Ejector return over limit
22.4 Ejection sequence not possible: robot consent missed
22.5 Ejector not out The ejection stroke didn't complete it's forward stroke Q19
22.6 Ejector not in The ejection stroke didn't complete it's backward stroke Q35 
22.7 Ejector security limit switch not activated The ejector return limit switch is activated but the input is missing. For Mega T it's SQ 112.
22.8 Core pulling sequence impossible ejector consent missed
22.9

 

 